How do we schedule fire extinguisher and fire alarm inspections for our HOA?

By OurHOA · General information · Revised

How an HOA board sets up fire extinguisher, fire alarm and sprinkler inspections: NFPA cycles, licensed vendors in TX and FL, tags, records and a yearly calendar.

Part of the HOA board handbook: vendors, projects and upkeep.

The short answer

Make a list of every extinguisher, alarm panel, detector and sprinkler system the association owns. Hire a licensed fire protection company to do the annual work on all of it in one visit, and have a volunteer do a short monthly walk of the extinguishers in between. Keep every report and tag in the association's records. The schedule itself comes from the national standards your local fire code adopts: NFPA 10 for portable extinguishers, NFPA 72 for fire alarms and NFPA 25 for sprinklers. The fire marshal can ask to see proof. A pool house with two extinguishers and a condo building with a fire alarm panel and a sprinkler riser are very different jobs, but the method is the same. Local code editions, amendments and your governing documents change the details, so confirm the cycle with your fire department. This guide is general education, not legal advice.

Start with an inventory and an ownership line

Walk every common building with a notepad and a camera. Count extinguishers by location and type, which is printed on the label. Note the fire alarm control panel, pull stations, smoke and heat detectors, horns and strobes, the monitoring communicator, any sprinkler riser, fire department connection, control valves and backflow assembly, and any kitchen hood suppression system in the clubhouse. Put it on one sheet with a column for the last service date from each tag. Then draw the ownership line. Systems that serve the building are usually common elements: the panel, corridor detectors, the riser and the heads fed from it. A battery or plug-in smoke alarm inside a unit is often the owner's, and in a single-family community the association usually owns fire equipment only in the clubhouse, pool house and similar buildings. Check the maintenance article of your declaration. Our guide on whether an HOA can charge you for a fire or life safety inspection covers how that split decides who pays and when the association can enter a unit.

The inspection calendar

For portable extinguishers, NFPA 10 calls for an inspection at installation and once a month after that, an annual maintenance examination by a certified person, an internal examination every 6 years for stored-pressure dry chemical units, and a hydrostatic test every 5 or 12 years depending on the type. The federal OSHA rule for employers, 29 CFR 1910.157, uses the same monthly and annual cycle and lists a 5-year hydrostatic test for carbon dioxide and water units and 12 years for stored-pressure dry chemical. An HOA with no employees is not an OSHA employer, but the table is a handy public reference for what your vendor should be doing. For fire alarm systems, NFPA guidance on NFPA 72 says system smoke detectors are inspected twice a year and functionally tested every year, with sensitivity testing a year after installation and then every other year. Adopted fire codes point to NFPA 72 for the rest of the system. Minnesota's version of the code, for one, requires fire alarm systems to be inspected and tested at least annually. Ask your fire department which edition and amendments apply to you. For sprinklers, NFPA's summary of NFPA 25 lists quarterly items such as the alarm valve exterior and fire department connection, an annual main drain test that moves to quarterly when the system is fed through a backflow or pressure reducing valve, and control valve checks monthly if locked or quarterly if electrically supervised. It also says the property owner or designated representative is responsible for this work. That is the board. For smoke alarms inside units, the U.S. Fire Administration tells residents to test them monthly and replace the entire alarm every 10 years. Put that line in an owner notice each fall even where owners maintain their own alarms.

Hire a licensed company, and check the license

In Texas, Insurance Code section 6001.151 says a firm may not install or service portable extinguishers unless it holds a registration certificate from the Texas Department of Insurance. The State Fire Marshal's Office licenses fire alarm firms under chapter 6002 and sprinkler firms under chapter 6003, and it publishes a license search. Its rule at 28 TAC 34.520 requires a service tag after any service showing the firm, license numbers, the work done and the month and year, and says only the registered firm or a regulator may remove the tag. Ask each bidder for the firm registration and the technician license numbers, and look them up before you sign. In Florida, Statutes section 633.304 requires anyone who services, recharges, repairs, hydrotests, installs, tests or inspects fire extinguishers to hold a permit from the Division of State Fire Marshal. Section 633.202 adopts NFPA 1 and NFPA 101 as the Florida Fire Prevention Code, updated every third year, and local governments enforce it. Colorado's Division of Fire Prevention and Control registers fire suppression contractors and sprinkler fitters under 8 CCR 1507-11, and that program excludes portable extinguishers. Extinguisher and alarm licensing is mostly local. Denver's fire code, for example, requires inspection records to show the Denver Fire Department license numbers of whoever did the work. Ask your fire district what license it expects. Bid it as one package if you can. A single company doing extinguishers, alarm and sprinklers on one day means one set of reports, one invoice and one person to call about a deficiency. Ask for a price per extinguisher for annual service, a separate price for 6-year and hydrostatic work, the hourly rate for deficiency repairs, and a copy of the certificate of insurance. Our guide on how to check a vendor certificate of insurance covers what to look for.

Monitoring, the fire marshal and Florida condos

If the alarm panel reports to a monitoring center, read that contract separately. Find the term and the auto-renewal date, who gets called when the alarm trips, and whether the monitoring company or the inspection company tests the signal to the center. Update the call list every time the board changes. Do not let a former director be the only contact. In many cities the fire marshal inspects common buildings on a set schedule or when a complaint comes in, and asks for the latest reports. Have a folder ready with the inventory, the last annual reports, proof that deficiencies were fixed and the monitoring certificate if you have one. How often your building gets a visit is set locally, so ask. Florida condominium boards carry an extra duty. Statutes section 718.112(2)(n) says an association must ensure compliance with the Florida Fire Prevention Code. It also requires high-rise residential condominiums to retrofit a fire sprinkler system or an engineered life safety system, unless the owners vote to forgo the sprinkler retrofit by a majority of all voting interests. If your building has been through that vote, keep the recorded certificate in the same folder, because the fire official will ask.

The monthly walk and the records

The monthly extinguisher check is a job a volunteer can do in twenty minutes with a clipboard. At each unit, confirm it is where the inventory says, nothing blocks it, the pin and seal are intact, the pressure gauge needle sits in the green, there is no visible damage or corrosion, and the service tag shows an annual date inside the last twelve months. Initial and date the log. Anything wrong goes to the vendor that week, not at the next annual visit. Keep the records in the association's files, not a director's email. That means the inventory, the monthly log, every annual report, deficiency quotes and proof of repair, and the monitoring contract. When the board turns over, the new president should be able to answer 'when were these last serviced' in one minute.

A sample year, a motion and the common mistakes

January: update the inventory and compare tag dates. February: send the bid package to two or three licensed companies. March: award the contract and set one annual service date. That month: annual extinguisher service, alarm test, sprinkler inspection and any 6-year or hydrostatic work that is due. Within 30 days: repair every listed deficiency and file proof. Monthly: volunteer extinguisher walk. Quarterly: sprinkler items where you have a system. October: owner notice on testing in-unit smoke alarms. A motion the board can adapt: 'Moved to retain [company], [Texas registration or Florida permit number], for annual inspection and testing of the association's fire extinguishers, fire alarm system and sprinkler system at the prices in its proposal dated [date], and to authorize [director] to approve deficiency repairs up to $[amount] per visit, with larger repairs to come back to the board.' The mistakes repeat. The board assumes the alarm company also services the extinguishers, and nobody does. The annual report lists deficiencies and it sits unread for a year. Someone hangs a kitchen extinguisher in the clubhouse that the vendor never inventoried. The monitoring center still calls a director who moved away. And the board pays an unlicensed handyman to 'check the extinguishers', which leaves no valid tag and no record the fire marshal will accept.

Sources

These guides are general education for HOA boards and residents, not legal, tax, or financial advice. Rules vary by state and by your community's governing documents - check with a professional for your situation.